Remote SIOS Peripherals
Analogue and digital I/Os for recording the process parameters
SIOS is a flexibly configured remote CAN peripheral device, adaptable to application, intelligent and future proof. A SIOS peripheral consists of at least one CAN gateway and one power module. The gateway and further I/O modules are powered by the first power module. SIOS modules consist of an I/O card and clamping module for wiring. Wiring takes place without tools via spring contacts. The modules are hot-swappable and can therefore be changed when energized.
The interchanging of modules is impossible due to the mechanical coding. There are SIOS gateways with different bus systems: SIOS-CAN as CAN bus systems and SIOS-TCPIP as an Ethernet bus system (in progress). A node consists of a maximum of 64 modules. The maximum number of nodes is 99. Because of the large number of nodes and the maximum number of 64 modules, the complete CANopen protocol can be utilized fully. Up to 25,344 digital I/Os or analogue values can be used in the maximum configuration per network, limited to one type of module.
SIOS-Features:
- Flexibly configured remote CAN peripheral device
- A peripheral consists of one CAN gateway and one power module
- Adjustment of desired digital/analogue I/Os by expandable I/O modules (maximum of 64 modules), consisting of I/O card and clamping module
- Spring-type terminal wiring
- Modules are hot-swappable and can therefore be changed when energized
- Interchanging of the I/O cards impossible due to mechanical coding gateway
Type: SIOS-CAN
Module: SIOS-GATEWAY
- Flexibly usable with up to 64 modules
- CANopen protocol
- Baud rates: 20 kB, 50kB, 100kB, 125 kB, 250 kB, 500 kB, 1MBaud
- CAN connection, galvanically isolated
- LED state for CAN communication, IO field comunication, energy supply
- Incl. power module SIOS PWRG
- Housing: 113 x 51 x 73 mm CAN gateway
Type: SIOS-PWRG / SIOS-PWR
Module: Supply Module
- Internal power supply for modules
- Input voltage: 24V DC (reverse polarity protected)
- Power supply of max. 16 modules (incl. power module)
- Modul options:
- SIOS-PWRG (for gateway supply and the first 16 modules)
- SIOS-PWR supply module (supply a further 16 modules incl. power module) - Dimensions with module: 128 x 12.7 x 74 mm
Type: SIOS-DI4
Module: 4 Digital Inputs
- Input voltage: 5 ... 24V for active level
- Input voltage with active level: approx. 3mA
- Galvanically isolated to internal field (max. 500V)
(no separation of inputs among each other) - Dimensions with module: 128 x 12.7 x 74 mm
Type: SIOS-DO4
Module: 4 Digital Outputs
- Supply voltage outputs: 7 ... 24V
- Output current: max. 700mA
- Short-circuit proof outputs
- Galvanically isolated to internal field (max. 500V)
(no separation of outputs among each other) - Dimensions with module: 128 x 12.7 x 74 mm
Type: SIOS-DAC2
Module: 2 Analogue Outputs
- Configurable as 0 - 10V, 0 - 20mA or 4 - 20mA
- 12 Bit resolution
- Output accuracy: better than 0.1% from the end of the range
- Current output: max. burden 500 Ohm
- Voltage output: min. burden 2KOhm
- Galvanically isolated to internal field (max. 500V)
(no separation of outputs among each other) - Dimensions with module: 128 x 12.7 x 74 mm
Type: SIOS-IW1-XL
Module: 1 Universal Analogue Input
- Galvanically isolated to internal Bus (max. 500V)
- Thermocouples, PT100, PT1000, potentiometer (max. 4kΩ)
- 18 Bit resolution
- Accuracy: better than 0.1% from the end of the range
- Measuring cycle per thermocouple or standard signal approx. 60ms
- Dimensions with module: 154 x 12.7 x 74 mm
Type: SIOS-IW2
Module: 2 Analogue Inputs (standard signal)
- 0 - 10V, 0 - 20mA, 4 - 20mA
- Accuracy: better than 0.1% from the end of the range
- Measuring cycle per input approx. 40 ms
- 18 Bit resolution
- Galvanically isolated to internal Bus (max. 500V)
(no separation of inputs among each other) - Dimensions with module: 128 x 12.7 x 74 mm